SM-A20758-A/3 1. PRODUCT OVERVIEW
21 2020-10-06
Diagnosis
Supplied power voltage is outside the rated
range.
(Detected at 19.5 VDC or less detection
accuracy ±10 %)
・Turn on the power again.
Input signal exceeds the rated range.
・Check the Input settings
・Turn on the power again.
Error occurred during memory reading or
writing.
・Turn on the power again.
Secondary side pressure does not maintain
the set value for five or more consecutive
seconds.
・Check that the primary side
pressure and the set value for
pressure.
・Turn on the power again.
・Check that there is no leakage
from the pipes, fittings, or other
components, correctly connect
the pipes and turn on the power
again.
Excessive operation of supply solenoid valve
・Check the operating
environment.
Excessive operation of supply solenoid valve
・Check the operating
environment.
Mode2 of switch output 1 is set with abnormal
threshold.
lower set value (L) > upper set value (H) - 10
(for more than 5 seconds)
・Check the threshold of switch
output 1.
Mode2 of switch output 2 is set with abnormal
threshold.
lower set value (L) > upper set value (H) - 10
(for more than 5 seconds)
・Check the threshold of switch
output 2.
Temperature of IO-Link driver is high.
・Check the operating
environment.