Setting Options Table
Volume
Capacity
Regeneration Time
Option
Day
Override
Result
1
AUTO NORMAL oFF
Reserve capacity automatically estimated.
Regeneration occurs when volume capacity falls below the reserve capacity at the next
Regen Set Time.
AUTO NORMAL Any number
Reserve capacity automatically estimated.
Regeneration occurs at the next Regen Set Time when volume capacity falls below the
reserve capacity or the speci ed number of days between regenerations is reached.
Any
number
NORMAL oFF
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when volume
capacity reaches 0.
oFF NORMAL Any number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when the speci ed number of days
between regenerations is reached.
Any
number
NORMAL Any number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when volume
capacity reaches 0 or the speci ed number of days between regenerations is reached.
AUTO on 0 oFF
Reserve capacity NOT automatically estimated.
Regeneration occurs immediately when volume capacity reaches 0. Time of
regeneration will not be allowed to be set because regeneration will always occur when
volume capacity reaches 0.
Any
number
on 0 oFF
Reserve capacity NOT automatically estimated.
Regeneration occurs immediately when volume capacity reaches 0. Time of
regeneration will not be allowed to be set because regeneration will always occur on 0.
AUTO NORMAL on 0 oFF
Reserve capacity automatically estimated.
Regeneration occurs when volume capacity falls below the reserve capacity at the next
Regen Set Time or regeneration occurs after 10 minutes of no water usage when volume
capacity reaches 0.
AUTO NORMAL on 0 Any number
Reserve capacity automatically estimated.
Regeneration occurs at the next Regen Set Time when volume capacity falls below the
reserve capacity or the speci ed number of days between regenerations is reached or
regeneration occurs after 10 minutes of no water usage when volume capacity reaches 0.
Any
number
NORMAL on 0 Any number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when the speci ed number of days
between regenerations is reached or regeneration occurs after 10 minutes of no water
usage when volume capacity reaches 0.
1
Reserve Capacity estimate is based on history of water usage. Reserve Capacity estimate is not available with
alternator systems or Twin Tank Valve.
Filters should only use shaded options

Questions and Answers: