CI Man u al Page 23
STEP 8D – MAV Drive History in the direction of extended piston
rod position. Display will not be shown if 1.0 is not selected in
Step 2CS and OFF is selected in Step 4CS. If the display does
appear up to a four digit number will appear after the “L” which
stands for latest and “A” which stands for average. Drive time is
measured in 1/100 of a second; i.e., a 17.10 second move is displayed as 1710. Press NEXT at any
time to go to Step 9D. Press REGEN to return to previous step.
STEP 7D
RETURN TO NORMAL MODE
When desired, all programming and all information in Diagnostics may be reset to defaults when the valve is installed in a
new location. To reset to defaults, press NEXT and buttons simultaneously to go to the Softening/Filtering screen. Press
and simultaneously to reset diagnostic values and all programming to defaults. Screen will return to User Display.
STEP 7D – Flow rate, maximum last seven days: The maximum ow rate in liters per minute that
occurred in the last seven days will be displayed. This display will equal zero if a water meter is not
installed. Press NEXT to go to Step 8D. Press REGEN to return to previous step.
STEP 8D
STEP 9D – MAV Drive History in the direction of retracted piston
rod position. Display will not be shown if 1.0 is not selected in Step
2CS and OFF is selected in Step 4CS. If the display does appear,
up to a four digit number will appear after the “L” which stands for
latest and “A” which stands for average. Drive time is measured in
1/100 of a second; i.e., a 17.15 second move is displayed as 1715. Press and hold and for 3
seconds while in Step 9D to reset the MAV drive history in both the extended and retracted piston
rod position. To view the old MAV drive history data see Step 8D. Press the NEXT button at any
time exit Diagnostics. Press REGEN to return to previous step.
STEP 9D
Press and hold and buttons for 3 seconds while in Step 8D to
reset the MAV drive history in both the retracted and extended piston
rod position. To view the old MAV drive history data for retracted
and extended rod position press and hold SET CLOCK and while
in Step 8D. Press NEXT to advance display to the old MAV drive
history.