Please apply the settings in the following sequence
Selections are made using the UP & DOWN buttons until the required setting is displayed,
After each setting press NEXT to continue or press REGEN to go back one stage.
Vessel Size 1044 1054 1252 1354 1465 1665 1865 2160 2469 3072 3672
Media Volume (Ltr) 37 37 50 62 75 100 125 150 300 450 650
Injector White White Blue Yellow Green Orange Lt Blue Lt Green Orange V3010-2D V3010-2E
DLFC usgpm 3.2 3.2 4.2 5.3 6.5 7.5 11 15 20 25 42
BLFC usgpm 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 2.2 2.2
Step 1, Cycle Sequence,
Press NEXT and DOWN simultaneously for 3 seconds and release.
Screen will display SOFTENING flashing
Press NEXT and DOWN simultaneously for three seconds, the screen should display SET 1, adjust to turbine setting below,
Set 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.5 1.5 2 2
Set (Alternating)
SET dp
Hardness
Set 1
Set 2
Set 3
Set 4
Set 5
Step 2. System Setup,
Press NEXT and DOWN simultaneously for 3 seconds and release.
SET with SOFTENING flashing should appear on screen.
Cycle 1 Backwash 12 15 15 15 15 15 15 15 15 20 20
Cycle 2 Brine dn 50 50 47 50 55 50 50 30 45 50 55
Cycle 3 Rinse 6 6 6 6 6 6 6 6 6 6 6
Cycle 4 Fill Kg 3.8 3.8 5 6.2 7.5 10 12.5 15 30 65
Cycle 4 Fill Mins 2" Only 16 24
Cycle 5
Set Capacity Kg 1.3 1.3 1.8 2.2 2.7 3.7 4.6 5.5 11.1 16.6 24
Set Regen
Set Time Regen
Set rLY 1 (Relay 1)
Set rLY 2 ( Relay 2)
Set Salt
Step 3, Display Settings.
Press NEXT & UP simultaneously for three seconds and release.