WS1, 1.5 & 2 Series Watersoftener
Installation Operation Maintenance Manual
SIMPWS1 REV3 13/07/11 PAGE 20 OF27
11.1.4 WS2 150-750 L
PARAMETER UNITS 150L 200L 250L 300L 350L 500L 750L
MAX.SERVICE
FLOW
M3/hr 6 8 10 12 14 20 24
SYSTEM
CAPACITY
Kg
CaCO3
7.5 10 12.5 15 17.5 25 37.5
CAPACITY @
300PPM
M3 25 33.4 41.75 50.1 58.45 83.5 125.2
5
SALT USED
PER REGEN
Kg 21 28 35 42 49 70 105
REGENERATIO
N TIME
MIN 96 120 120 140 140 140 140
SALT STORAGE
CAPACITY
Kg 300 400 500 500 750 750 1000
MAX
OPERATING
TEMP
O
C 50 50 50 50 50 50 50
MAX FLOW TO
DRAIN
LIT/MIN 26.5 37.85 37.85 56.78 56.78 94.63 132.4
8
IMPORTANT NOTES
Much of the data quoted in the above table is affected by the inlet pressure,
and so should be regarded as nominal only.
Total flow to drain will be similarly affected and is therefore not quoted, but
will be about 6 times the resin volume.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Clack WS1 Series and is the answer not in the manual?

Clack WS1 Series Specifications

General IconGeneral
SeriesWS1
RegenerationUpflow
CertificationsNSF/ANSI 44
Operating Temperature34 - 120°F (1 - 49°C)
Power Supply12 VAC
TypeWater Softener