Page 10 WS1CS & WS1.25CS Manual
4
Reserve capacity estimate is based on history of water usage.
Setting Options Table
Volume
Capacity
Regeneration
Time Option
Day
Override
Result
4
AUTO NORMAL oFF
Reserve capacity automatically estimated.
Regeneration occurs when volume capacity falls below the reserve
capacity at the next Regen Set Time
AUTO NORMAL
Any
number
Reserve capacity automatically estimated.
Regeneration occurs at the next Regen Set Time when volume capacity
falls below the reserve capacity or the speci ed number of days between
regenerations is reached.
Any
number
NORMAL oFF
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when volume
capacity reaches 0.
oFF NORMAL
Any
number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when the speci ed
number of days between regenerations is reached.
Any
number
NORMAL
Any
number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when volume
capacity reaches 0 or the speci ed number of days between
regenerations is reached.
AUTO On 0 oFF
Reserve capacity not automatically estimated.
Regeneration occurs immediately when volume capacity reaches 0.
Time of regeneration will not be allowed to be set because regeneration
will always occur when volume capacity reaches 0.
Any
number
On 0 oFF
Reserve capacity not automatically estimated.
Regeneration occurs immediately when volume capacity reaches 0.
Time of regeneration will not be allowed to be set because regeneration
will always occur on 0.
AUTO NORMAL + on 0 oFF
Reserve capacity automatically estimated.
Regeneration occurs when volume capacity falls below the reserve
capacity at the next Regen Set Time or regeneration occurs after 10
minutes of no water usage when volume capacity reaches 0.
AUTO NORMAL + on 0
Any
number
Reserve capacity automatically estimated.
Regeneration occurs at the next Regen Set Time when volume capacity
falls below the reserve capacity or the speci ed number of days between
regenerations is reached or regeneration occurs after 10 minutes of no
water usage when volume capacity reaches 0.
Any
number
NORMAL + on 0
Any
number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when the speci ed
number of days between regenerations is reached or regeneration occurs
after 10 minutes of no water usage when volume capacity reaches 0.
Filters should only use shaded options