TSM/TSL Vertical Stack
Rev.: January 18, 2021
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Blower Performance Data – TSM18
Table 5d
All data is presented as lowest of nameplate voltage.
All data is shown wet coil with clean 1” lter.
All data is ran at 80°F DB and 67°F WB.
CFM Tolerance is 7%.
RPM/Watt Tolerance 10%.
Denotes Operation not recommended.
External Static Pressure (in. wg)
PSC - Low Static
Speed Tap 0.0 0.1 0.2 0.3
Low
RPM
Power (W)
CFM
Medium
RPM 600 660 730 810
Power (W) 182 176 170 165
CFM 520 500 470 440
High
RPM 750 790 840 900
Power (W) 221 212 203 194
CFM 660 630 600 570
ECM - Constant Torque
Speed Tap 0.0 0.1 0.2 0.3
1
RPM 650
Power (W) 57
CFM 460
2
RPM 730 760 810
Power (W) 70 80 80
CFM 530 500 470
3
RPM 790 820 870 920
Power (W) 97 97 107 107
CFM 580 550 520 490
4
RPM 880 920 950 1000
Power (W) 137 137 147 147
CFM 650 630 600 580
5
RPM 950 990 1030 1070
Power (W) 177 177 187 187
CFM 710 690 670 650
ECM - Constant Volume
CFM 0.0 0.1 0.2 0.3
450
RPM 530 640 740 820
Power (W) 29 43 56 69
500
RPM 600 690 780 860
Power (W) 39 52 65 78
600
RPM 660 740 820 900
Power (W) 51 65 79 93
700
RPM 720 800 870 940
Power (W) 67 81 95 109
800
RPM 790 850 910 980
Power (W) 86 100 115 130