EasyManua.ls Logo

ClimateMaster Tranquility TSM Series - Page 44

ClimateMaster Tranquility TSM Series
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
TSM/TSL Vertical Stack
Rev.: January 18, 2021
ClimateMaster Water-Source Heat Pumps
44
Blower Performance Data – TSM24
Table 5e
All data is presented as lowest of nameplate voltage.
All data is shown wet coil with clean 1” lter.
All data is ran at 80°F DB and 67°F WB.
CFM Tolerance is 7%.
RPM/Watt Tolerance 10%.
Denotes Operation not recommended.
External Static Pressure (in. wg)
PSC - Low Static
Speed Tap 0.0 0.1 0.2 0.3
Low
RPM
Power (W)
CFM
Medium
RPM 640 690 750 820
Power (W) 236 227 217 208
CFM 690 670 640 590
High
RPM 710 760 820 880
Power (W) 297 285 272 260
CFM 860 840 810 770
ECM - Constant Torque
Speed Tap 0.0 0.1 0.2 0.3
1
RPM 640 690 730
Power (W) 62 68 76
CFM 710 660 600
2
RPM 690 730 780 850
Power (W) 89 97 102 109
CFM 820 770 720 670
3
RPM 740 780 830 890
Power (W) 120 129 134 143
CFM 930 880 830 790
4
RPM 830 880 920
Power (W) 169 173 185
CFM 990 950 910
5
RPM
Power (W)
CFM
ECM - Constant Volume
CFM 0.0 0.1 0.2 0.3
600
RPM 600 660 730 830
Power (W) 70 87 104 122
700
RPM 640 700 770 860
Power (W) 96 115 134 153
800
RPM 680 750 820 890
Power (W) 122 143 164 184
900
RPM 720 790 860 920
Power (W) 155 176 197 218
950
RPM 740 810 880 930
Power (W) 193 214 234 255