TSM/TSL Vertical Stack
Rev.: January 18, 2021
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Blower Performance Data – TSM30
Table 5f
All data is presented as lowest of nameplate voltage.
All data is shown wet coil with clean 1” lter.
All data is ran at 80°F DB and 67°F WB.
CFM Tolerance is 7%.
RPM/Watt Tolerance 10%.
Denotes Operation not recommended.
External Static Pressure (in. wg)
PSC - Low Static
Speed Tap 0.0 0.1 0.2 0.3
Low
RPM 860 850 890 930
Power (W) 344 328 311 295
CFM 1010 980 940 880
Medium
RPM 920 910 940 970
Power (W) 385 365 345 325
CFM 1100 1070 1020 960
High
RPM 1090
Power (W) 422
CFM 1240
ECM - Constant Torque
Speed Tap 0.0 0.1 0.2 0.3
1
RPM 770 770 800
Power (W) 105 113 118
CFM 880 830 780
2
RPM 860 840 880 940
Power (W) 151 158 165 170
CFM 1000 960 920 900
3
RPM 950 920 960 1000
Power (W) 210 217 225 229
CFM 1140 1100 1070 1030
4
RPM 1000 1040 1060
Power (W) 285 295 299
CFM 1230 1200 1160
5
RPM
Power (W)
CFM
ECM - Constant
Volume
CFM 0.0 0.1 0.2 0.3
750
RPM 690 720 790 880
Power (W) 109 133 157 182
875
RPM 770 790 860 930
Power (W) 157 183 209 235
1000
RPM 860 870 930 990
Power (W) 219 247 275 303
1100
RPM 920 920 980 1030
Power (W) 310 336 361 387