Electrical – Line Voltage, Cont’d.
Table 4d: Tranquility
®
20 (TS) Series Electrical Data - (PSC Motor & Secondary Pump)
All TS Units with Standard PSC Motor TS Units (PSC)
TS Units with PSC Fan Motor
and Secondary Pump
Model
Voltage
Code
Rated
Voltage
Voltage
Min/Max
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
QTY RLA LRA
006
G 208/230/60/1 197/254 1 3.1 17.7 0.4 3.5 4.3 15 0.4 3.9 4.7 15
E 265/60/1 239/292 1 2.6 13.5 0.4 3.0 3.6 15 0.7 3.7 4.3 15
009
G 208/230/60/1 197/254 1 3.9 21.0 0.4 4.3 5.3 15 0.4 4.7 5.7 15
E 265/60/1 239/292 1 3.7 22.0 0.4 4.1 5.0 15 0.7 4.8 5.7 15
012
G 208/230/60/1 197/254 1 5.0 25.0 0.7 5.7 7.0 15 0.4 6.1 7.4 15
E 265/60/1 239/292 1 4.5 22.0 0.7 5.2 6.4 15 0.7 5.9 7.0 15
018
G 208/230/60/1 197/254 1 9.0 48.0 1.0 10.0 12.3 20 0.4 10.4 12.7 20
E 265/60/1 239/292 1 8.4 40.0 0.9 9.3 11.4 15 0.7 10.0 12.1 20
024
G 208/230/60/1 197/254 1 13.5 58.3 1.6 15.1 18.5 30 0.4 15.5 18.9 30
E 265/60/1 239/292 1 9 54.0 1.1 10.1 12.4 20 0.7 10.8 13.1 20
H 208/230/60/3 197/254 1 7.1 55.4 1.6 8.7 10.5 15 0.4 9.13 10.9 15
F* 460/60/3* 414/506 1 3.5 28.0 0.9 4.4 5.3 15 0.7 5.1 6.0 15
030
G 208/230/60/1 197/254 1 12.8 64.0 1.8 14.6 17.8 30 0.8 15.4 18.6 30
E 265/60/1 239/292 1 10.9 60.0 1.4 12.3 15.0 25 0.7 13.0 15.7 25
H 208/230/60/3 197/254 1 8.3 58.0 1.8 10.1 12.2 20 0.8 10.9 13.0 20
F* 460/60/3* 414/506 1 5.1 28.0 1.0 6.1 7.4 15 0.7 6.8 8.1 15
036
G 208/230/60/1 197/254 1 16.0 77.0 1.8 17.8 21.8 35 0.8 18.6 22.6 35
E 265/60/1 239/292 1 12.2 72.0 2.0 14.2 17.3 25 0.7 14.9 18.0 30
H 208/230/60/3 197/254 1 10 71.0 1.8 11.8 14.3 20 0.8 12.6 15.1 25
F* 460/60/3* 414/506 1 4.7 38.0 1.0 5.7 6.9 15 0.7 6.4 7.6 15
042
G 208/230/60/1 197/254 1 16.7 79.0 2.2 18.9 23.1 35 0.8 19.7 23.9 40
E 265/60/1 239/292 1 13.5 72.0 1.7 15.2 18.6 30 0.7 15.9 19.3 30
H 208/230/60/3 197/254 1 10.4 73.0 2.2 12.6 15.2 25 0.8 13.4 16.0 25
F* 460/60/3* 414/506 1 5.8 38.0 1.0 6.8 8.3 15 0.7 7.5 9.0 15
N 575/60/3 518/633 1 3.8 36.5 0.8 4.6 5.6 15 N/A N/A N/A N/A
048
G 208/230/60/1 197/254 1 21.8 117.0 2.7 24.5 30.0 50 0.8 25.3 30.8 50
E 265/60/1 239/292 1 16.3 98.0 2.9 19.2 23.3 35 0.7 19.9 24.0 40
H 208/230/60/3 197/254 1 13.7 83.1 2.7 16.4 19.8 30 0.8 17.2 20.6 30
F* 460/60/3* 414/506 1 6.2 41.0 1.7 7.9 9.5 15 0.7 8.6 10.2 15
N 575/60/3 518/633 1 4.8 33.0 1.4 6.2 7.4 15 N/A N/A N/A N/A
060
G 208/230/60/1 197/254 1 26.4 134.0 3.8 30.2 36.8 60 1.1 31.3 37.9 60
H 208/230/60/3 197/254 1 16 110.0 3.8 19.8 23.8 35 1.1 20.9 24.9 40
F* 460/60/3* 414/506 1 7.8 52.0 1.3 9.1 11.1 15 1.3 10.4 12.4 20
N 575/60/3 518/633 1 5.7 38.9 2.2 7.9 9.3 15 N/A N/A N/A N/A
070
G 208/230/60/1 197/254 1 30.8 178.0 4.0 34.8 42.5 70 1.1 35.9 43.6 70
H 208/230/60/3 197/254 1 19.6 138.0 4.0 23.6 28.5 45 1.1 24.7 29.6 45
F* 460/60/3* 414/506 1 8.2 66.1 2.6 10.8 12.9 20 1.3 12.1 14.2 20
N 575/60/3 518/633 1 6.6 55.3 1.5 8.1 9.8 15 N/A N/A N/A N/A
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with internal secondary circulators require a four wire power supply with neutral.
Internal secondary circulators are rated 265 vac and are wired between one hot leg and neutral.