Size 20.4-25.4-30.4 Combustion module - CAK and CBK conguration
1. Compressor compartment
2. Electrical panel
3. Condensate drain
4. Functional clearances
5. Internal exchanger
6. External exchanger
7. H2O heating coil / Electric heaters (Optional)
8. Re-heating coil (Optional)
9. G4 air lters (Standard)
10. F7 bag lters / H10 electronic air lters (Optional)
11. Electric fan (Supply - return)
12. External electric fan
13. Outdoor air damper (CBK cong.)
14. Access for inspection of coils, lters, heating elements
15. Lifting brackets (removable)
16. Humidier connections
17. H2O heating coil input Ø 1”1/4
18. H2O heating coil output Ø 1”1/4
19. Gas module
(RO) Horizontal air return
(R3) FLoor air inlet (optional)
(M0) Horizontal air supply
(AE) Outdoor air return (only for CBK conguration)
(H1) Wall with same height as unit on a maximum of three sides
(**) Suggested clearance
(*) Vibration mounts position
Size 20.4 25.4 30.4
Conguration CAK/CBK CAK/CBK CAK/CBK
W1 supporting point kg 391 400 403
W2 Supporting point kg 294 302 304
W3 Supporting point kg 336 345 347
W4 Supporting point kg 405 414 417
Operating weight kg 1426 1461 1471
Shipping weight kg 1426 1461 1471
The presence of optional accessories may result in a substantial variation of the weights shown in the table.
GAS MODULE WEIGHT DISTRIBUTION
Size 24.4 25.4 30.4
W5 Supporting point 75 75 75
W6 Supporting point kg 63 63 63
W7 Supporting point kg 63 63 63
W8 Supporting point kg 75 75 75
Operating weight kg 1702 1737 1747
Shipping weight kg 1426 1461 1471
