TROUBLESHOOTING
106
BH
Description
PED PCB faulty
The unit shuts down.
The error code is displayed on the main PCB and user interface.
Possible causes
Power supply problem.
PED board faulty.
IPM module faulty
bH
Power supply problem.
After 5 minutes of shut down, switch on again and
check whether the problem can be solved.
YES
Increase the power supply voltage to the required
value.
NO
PED board faulty.
YES
Replace the PED PCB and switch on again.
NO
IPM module faulty.
YES
Replace the IPM module and switch on again.