TROUBLESHOOTING
PP - Hb
Description
Water side heat exchanger inlet temperature is higher than outlet temperature in heating mode.
The unit shuts down.
The error code is displayed on the main PCB and user interface.
Hb indicates that PP has been displayed 3 times.
Possible causes
Temperature sensor not connected properly or has malfunctioned.
4-way valve is blocked or damaged.
Main PCB is damaged.