TROUBLESHOOTING
66
F1
Description
Low DC generatrix voltage.
The unit shuts down.
The error code is displayed on the main PCB and user interface.
Possible causes
DC generatrix voltage is too low
Procedure
F1
Power supply is abnormal
YES
Provide normal power
NO
The LED on the inverter
modules is lit
YES
The PN voltage is 380V
YES
Check the main board
NO
The input power of inverter
module is abnormal
YES
The main board is damaged
and must be replaced
NO
The inverter module is
damaged and must be
replaced