TROUBLESHOOTING
98
Situation 3: L0 error is displayed within 2 seconds of compressor startup
L0
U V W wire between inverter module and
compressor is not connected properly (1)
YES
Ensure U V W wire is connected properly
NO
The communication port for connection to the
inverter module on the refrigerant circuit board is
damaged (2)
YES
Replace main PCB
NO
Replace main PCB
Notes:
1. Connect the U V W wire from the inverter module to the correct compressor terminals, as indicated by the
labels on the compressor
2. Measure the voltage between W-, W+, V-, V+, U-, U+ and GND when the unit is in standby. The normal voltage
should be 2.5 V-4 V and the six voltages should be the same, otherwise the communication terminal is faulty.
Inverter module connection port