IGS-NT Combi, SW Version 3.0, ©ComAp May 2013
IGS-NT-Combi-3.0 Reference Guide.PDF
164
Setpoint: ExctLoss del
Group
Gener protect
Range [units]
OFF, 0.1 .. 600.0 [s]
Related FW
3.0
Force value
possible
YES
Description
This setpoint adjusts the delay for loss of excitation protection. Threshold of this
protection is given by the setpoint ExcitationLoss.
Setpoint: Gen V unbal
Group
Gener protect
Range [units]
0 .. 200 [%]
Related FW
3.0
Description
This setpoint adjusts the threshold level for the generator voltage unbalance
protection. The threshold is adjusted in % of the nominal generator voltage, which
is either GenNomV or GenNomVph-ph, depending on the position of the setpoint
FixVoltProtSel. The protection is Breaker open and cool down type and is created
in the default archive as universal analog protection at the value Gen V unbal,
which is calculated as maximum difference between two phase voltages.
The protection activates if the voltage unbalance gets over the threshold for time
longer than Gen V unb del.
NOTE:
The voltage unbalance protection is created in the default archive using the
mechanism of universal analog protections. That means this setpoint is one of
general-purpose setpoints, which may be used for different purpose if the
protection is deleted from the configuration.
Setpoint: Gen V unb del
Group
Gener protect
Range [units]
0.0 .. 600.0 [s]
Related FW
3.0
Description
This setpoint adjusts the delay for the generator voltage unbalance protection.
The threshold for the protection is adjusted by setpoint Gen V unbal.
NOTE:
The generator voltage unbalance protection is created in the default archive using
the mechanism of universal analog protections. That means this setpoint is one
of general-purpose setpoints, which may be used for different purpose if the
protection is deleted from the configuration.
Setpoint: Gen I unbal
Group
Gener protect
Range [units]
0 .. 200 [%]