Although the resolution of this setpoint is 0.01s, in fact the adjusted delay is 
rounded to the next higher multiple of the period of the mains voltage. The period 
is either 0.02s for 50Hz systems or 0.0166s for 60Hz systems. E.g. if the delay is 
set to 0.03s at 50Hz system the real delay will be 0.04s.  
 
 
Setpoint: VectorS prot 
DISABLED, PARALLEL ONLY, ENABLED [-] 
This setpoint selects the function of the built-in vectorshift protection. 
 
The vectorshift protection is disabled. 
The vectorshift protection is enabled only while the gen-set 
is running parallel to the mains, i.e. the both MCB and GCB 
are closed.  
The vectorshift protection is active always while the MCB is 
closed, regardless of the GCB position. 
 
NOTE:  
The vectorshift protection is recorded into the history file, however it is not 
indicated in the Alarm list. When it occurs the controller opens either MCB or GCB 
depending on the setpoint VS/ROCOF CB sel (in SPI aplication GCB is always 
opened, VS/ROCOF CB sel setpoint is not available). If the MCB is not controlled 
in the particular application then GCB is opened. 
 
NOTE:  
If a vectorshift is detected and consequently the MCB is opened, however mains 
voltage and frequency remain in limits, the MCB is then reclosed again after 
Mains ret del, as the mains is evaluated as healthy.  
 
 
Setpoint: VS/ROCOF CBsel 
This setpoint selects which breaker will be opened when the vectorshift or 
ROCOF protection is detected. 
NOTE:  
If the GCB is selected and a mains failure occurs the GCB will be opened 
immediately when the vectorshift or ROCOF is detected, however also MCB will 
be opened consequently due to other mains protection as underfrequency or 
undervoltage.