IGS-NT Combi, SW Version 3.0,   ©ComAp – May 2013                    
IGS-NT-Combi-3.0 Reference Guide.PDF 
 
 
Binary output: Cooling Pump 
This output is used for control of an external electric motor-driven cooling pump. 
The output closes when the gen-set is started (i.e. at the end of the Starting 
period) and opens at the end of the Aftercooling period, which takes place after 
the engine has been fully stopped. Duration of the aftercooling period is adjusted 
by the setpoint AfterCool time. 
The output opens immediately when Emergency stop is activated or if the 
controller is switched to OFF mode. 
 
Binary output: GCB Close/Open 
This output is intended for control of the GCB if a contactor is used as GCB. The output 
provides continuous signal while the GCB has to be closed. 
There are also other outputs availabe for GCB control:  
  GCB ON coil 
  GCB OFF coil 
  GCB UV coil 
 
 
TIMING OF BREAKER CONTROL OUTPUTS 
 
 
Binary output: GCB ON Coil