IGS-NT Combi, SW Version 3.0,   ©ComAp – May 2013                    
IGS-NT-Combi-3.0 Reference Guide.PDF 
 
This output is closed while the application is currently running in SPI mode. See 
the chapter Description of Combi application for information how to switch the 
application mode. 
 
Binary output: SPtM mode 
This output is closed while the application is currently running in SPtM mode. See 
the chapter Description of Combi application for information how to switch the 
application mode. 
 
Binary output: MINT mode 
This output is closed while the application is currently running in MINT mode. See 
the chapter Description of Combi application for information how to switch the 
application mode. 
 
Binary output: Vgen <> 
The output is closed while the generator over/under voltage alarm is present in the 
alarm list. 
 
Binary output: Vmains <> 
The output is closed while the mains over/under voltage alarm is present in the 
alarm list. 
 
Binary output: Overcurrent 
The output is closed while there is either the Generator IDMT Overcurrent or 
Generator Short current alarms present in the alarm list. 
 
Binary output: VectorShiftTrp 
The output closes if the Vector shift protection gets active and the controller trips 
the selected breaker. The output stays closed for 3s, then opens again. 
NOTE:  
See also the output VectorShiftAct.  
 
 
Binary output: VectorShiftAct 
The output closes if the Vector shift protection gets active. It stays closed for 3s,