15.  Sensors 
15.1.  Sensor fail detection (FLS)  
If the measured resistance, voltage or current on an analog input gets out of valid range, the 
sensor fail will be detected and a sensor fail message will appear in the alarmlist. The valid 
range is defined by the most-left (R
L
) and most-right (R
H
) points of the sensor characteristic 
±12.5% from R
H
-R
L
. 
12.5% of the
sensor
range (25Ω) 
Sensor fail limit would be 
-15 Ω what is physically
imposible so sensor fail is
not detected even for 0 ohm
First point of
the curve
100% of the sensor range
Last point of 
the curve
Sensor fail
limit
Sensor fail area
10
11,25
Bar
10
210
235
Ω 
12.5% of the
sensor
range (25Ω)
-15
 
HINT 
The sensor fail alarm does not influence the gen-set operation. Sensor fail does not activate 
Binary output Alarm. 
If engine shutdown/stop is required when Fls appears, configure in GenConfig -> 
Inputs/Outputs -> Analog inputs -> Protection -> property “Active when” to Under/Over limit + 
Fls. 
15.2.  Default Sensors 
There are several predefined sensors which can be used for connection of particular sensor 
to analog inputs of the controller. The following list shows predefined standard sensors which 
are available in the roller menu. 
PT100/°C, PT1000/°C, PT100/°F, PT1000/°F, NI1000/°C, NI1000/°F, 4-20mA active (linear), 
0-2400ohm (linear), 0-2.4V (linear), Tristate (for definition please see the chapter about wiring 
Analog Inputs) 
If you click on Other sensors, following dialog is shown: