Mechanical dimensions:      96 x 27 x 43 mm , DIN rail (35 mm) mounted 
20.11.1.  IG-AVRi Trans/LV 
Primary voltage 1:        230-277 VAC 
Absolute low limit:        230 VAC – 20% 
Absolute high limit:        277 VAC + 20% 
 
Primary voltage 2:        400-480 VAC 
Absolute low limit:        400 VAC – 20% 
Absolute high limit:        480 VAC + 20% 
 
Frequency:          50 – 60 - 400 Hz 
Secondary voltage:        18 V AC, 5 VA 
Operating temperature      -30..+70
o
C 
20.11.2.  IG-AVRi Trans/100 
Primary voltage:        100 – 120 VAC  
Absolute low limit:        100 VAC – 20% 
Absolute high limit:        120 VAC + 20% 
 
Frequency:          50 - 60 – 400Hz 
Secondary voltage:        18 V AC 
Operating temperature      -30..+70
o
C 
20.12.  IGS-PTM   
Voltage supply        8-36V DC 
Consumption          0,1A depend on supply voltage 
Mechanical dimensions:      40 x 9 x 45 mm , DIN rail (35 mm) mounted 
Interface to controller       CAN 
Operating temperature       -30..+70
o
C 
20.12.1.  Binary inputs 
Number of inputs             8 
Input resistance            4,7 k 
Input range              0 - 36 VDC 
Switching voltage level for close contact indication   0 - 2 V 
Max voltage level for open contact indication    8-36 V 
20.12.2.  Binary open collector outputs 
Number of outputs          8 
Maximum current          0,5 A 
Maximum switching voltage        36 VDC