7)  When gen-set is running unloaded increase carefully Voltage gain to unstable point 
and then decrease value by 30 %  to insure stable performance. 
8)  Adjust Voltage int (usually setting to 100% gives optimal performance). 
 
Hint: 
To judge optimal adjusting induce generator voltage jumps by AVR DCout bias change or by 
Nominal voltage change.  
AVRi output OCOM is a common output. GND was used instead of OCOM 
17.2.3.  PF control adjustment 
The genset should be cca 30 % loaded in parallel to mains and baseload mode. 
1)  Set the same values PF gain, PF int as in voltage control loop. 
2)  Set Process control: #SysLdCtrl PtM = BASELOAD, #SysBaseLoad = 30 % of 
Nominal load,    #SysPFCtrl PtM = BASEPF,  #SysPwrFactor  = 1.0. 
3)  Start and synchronize the gen-set in MAN Mode by pressing GCB ON/OFF  
4)  When running in parallel 30% loaded increase slowly PF gain to unstable point and 
then  decrease value by 30 %  to insure stable performance. 
5)  Adjust PF int (usually setting to 100% gives optimal performance). 
Hint: 
To judge optimal adjusting  induce generator power jumps by SysBaseLoad change or by 
soft changes of AVR DCout bias.