IGS-NT Installation Guide  
 
7.5.2.  Terminals, Inputs and Outputs 
3x120 / 277 Ph-N or 207 / 480 Ph-Ph VAC 
(neutral not needed),  max 350 / 600VAC *, 
CAT III 
3x120 / 277 Ph-N or 207 / 480 Ph-Ph VAC 
(neutral not needed),  max 350 / 600VAC, 
CAT III 
L1k,L1l, L2k,L2l, 
L3k,L3l 
0 ÷ 5 Amps, max 10 A all time, 150 A for 2 
sec 
0 ÷ 1 Amp, max 2 Amps all time  
0 ÷ 5 Amps, max 10 A all time, 150 A for 2 
sec 
0 ÷ 1 Amp, max 2 Amps all time 
TTL (5V PWM) interface to IG-AVRi 
Activation to minus power supply. 
Load is connected to plus or to minus power 
supply. (defined in GenConfig). 
Speed governor output interface (10V / 5V 
PWM; 500 – 3000Hz) 
Min 2 Vpk-pk (from 4 Hz to 4 kHz) 
PC: InteliMonitor, GenConfig or 
Modem, GSM modem or 
ECU (e.g. Cummins ModBus) or InteliVision 
8 
Up to 3 IS-Displays (Remote display), up to 3 
InteliVision 8  displays (remote display) or 3 
InteliVision 5. 
 
Redirected RS232 (2) – see Basic settings: 
RS485(2)conv. 
PC: InteliMonitor, GenConfig  
or Modem, GSM modem or InteliVision 8 
PC: InteliMonitor, GenConfig 
Extension modules: IS-AIN, IS-BIN,IGS-
PTM, IGL-RA15, I-AOUT 
Intercontroller (Load&VAR sharing, Power 
management), monitoring (IG-IB, I-LB) and 
up to 4 InteliVision 8 
Remote monitoring via Ethernet, 
InteliMonitor, WebSupervisor and etc…