IGS-NT Installation Guide  
 
7.7.2.  Terminals, Inputs and Outputs 
3x120 / 277 Ph-N or 207 / 480 Ph-Ph VAC  
(neutral not needed),  max 350 / 600VAC*, 
CAT III 
3x120 / 277 Ph-N or 207 / 480 Ph-Ph VAC  
(neutral not needed),  max 350 / 600VAC, 
CAT III 
L1k,L1l, L2k,L2l, 
L3k,L3l 
0 ÷ 5 Amps, max 10 A all time, 150 A for 2 
sec 
0 ÷ 1 Amp, max 2 Amps all time  
0 ÷ 5 Amps, max 10 A all time, 150 A for 2 
sec 
0 ÷ 1 Amp, max 2 Amps all time 
Activation to minus power supply. 
Load is connected to plus power supply. 
PC: InteliMonitor, GenConfig or 
Modem, GSM modem or 
ECU (e.g. Cummins ModBus) or InteliVision 
8 
RS485 (1) ** 
non isolated 
IG-Display (Remote display) or InteliVision 8 
(remote display) or for PC (via RS485 
converter) = redirected RS232 (1)  
see Basic settings: RS485(1)conv. 
For IG-Display and InteliVision 8, the 
setpoint RS485 (1) conv has to be set to 
DISABLED value. 
Extension modules: IS-AIN8, IS-
BIN16/8,IGS-PTM, IGL-RA15, I-AOUT8 
Intercontroller (Load&VAR sharing, Power 
management) and monitoring (IG-IB, I-LB) 
and up to 4 InteliVision 8 displays 
NOTE:  
* IG-MTU or IG-MTU-2-1 can be used for three wire systems, systems with separated 
Neutral or when galvanic separation between generator or mains voltage and controller is 
required. 
** When more devices connected to RS485 bias resistor jumpers should be closed only on 
one of them.