IGS-NT Installation Guide  
Resistance input 0-2400 Ω 
For more info see the chapter 
Speed Governor Output 
7.1.2.  Terminals, Inputs and Outputs 
3x 277 Ph-N or 480 Ph-Ph VAC  
(neutral not needed),  max 350 / 600VAC *, 
CAT III 
3x 277 Ph-N or 480 Ph-Ph VAC  
(neutral not needed),  max 350 / 600VAC, 
CAT III 
L1k,L1l, L2k,L2l, 
L3k,L3l 
0 ÷ 5 Amps, max 10 A all time, 150 A for 2 
sec 
0 ÷ 5 Amps, max 10 A all time, 150 A for 2 
sec 
TTL (5V PWM) interface to IG-AVRi 
Activation to minus power supply. 
Load is connected to plus power supply. 
Speed governor output interface (10V / 5V 
PWM; 500 – 3000Hz) 
Min 2 Vpk-pk (from 4 Hz to 4 kHz) 
PC: InteliMonitor, GenConfig or 
Modem, GSM modem or 
ECU (e.g. Cummins ModBus) or InteliVision 
8 
IG-Display (Remote display) or InteliVision 8 
(remote display) or for PC (via RS485 
converter) = redirected RS232 (1)  
see Basic settings: RS485(1)conv. 
For IG-Display and InteliVision 8, the setpoint 
RS485 (1) conv has to be set to DISABLED 
value. 
Extension modules: IS-AIN, IS-BIN,IGS-
PTM, IGL-RA15, I-AOUT 
Intercontroller (Load&VAR sharing, Power 
management) and monitoring (IG-IB, I-LB) 
and up to 4 InteliVision 8 displays 
NOTE:  
* IG-MTU or IG-MTU-2-1 can be used for three wire systems, systems with separated 
Neutral or when galvanic separation between generator or mains voltage and controller is 
required.