IGS-NT-BC, SW Version 1.2.0, ©ComAp – January 2019
IGS-NT-BC-1.2.0 Reference Guide.PDF
in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load res
3 and Load res 4. If none of these inputs is active the set #1 is selected.
NOTE:
The reserve for stop must be always adjusted higher than the reserve for start.
This setpoint is used to adjust the load reserve for start in relative mode. i.e. Pwr
mgmt mode = REL (%) if the reserve set #4 is active. Learn more about reserves
in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load res
3 and Load res 4. If none of these inputs is active the set #1 is selected.
This setpoint is used to adjust the load reserve for stop in relative mode. i.e. Pwr
mgmt mode = REL (%) if the reserve set #4 is active. Learn more about reserves
in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load res
3 and Load res 4. If none of these inputs is active the set #1 is selected.
NOTE:
The reserve for stop must be always adjusted higher than the reserve for start.
This setpoint is used to adjust the delay of starting the next gen-set when the
actual load reserve drops below the adjusted reserve for start, but the group is still
not overloaded.