IGS-NT Communication Guide
105
7.4.13 User & Password in two steps
Request: 01 06 18 DA 00 00 AE 91
01 = controller address
06
= Modbus function code (Write Single Registers
(page 137))
18 DA
= Register address: Object for user identification
(46363) 40001 = 6362 DEC => 18DA HEX
00 00 = ID of user; Administrator = 00 => 0000
91 AE
= Check field calculation (page 143) (write LSB MSB
!)
Response: 01 06 18 DA 00 00 AE 91
01 = Controller address
06 = Modbus command
18 DA = Register address
00 00 = Release value
91 AE = CRC
Request: 01 06 18 DB 00 00 FF 51
01 = controller address
06
= Modbus function code (Write Single Registers
(page 137))
18 DB
= Register address: Object for entering password
(46364) 40001 = 6363 DEC => 18DB HEX
00 00 = Password = 00 => 0000
51 FF
= Check field calculation (page 143) (write LSB MSB
!)
Response: 01 06 18 DB 00 00 FF 51
01 = Controller address
06 = Modbus command
18 DB = Register address
00 00 = Release value
51 FF = Check field calculation (page 143)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliGen NT BaseBox and is the answer not in the manual?

ComAp InteliGen NT BaseBox Specifications

General IconGeneral
BrandComAp
ModelInteliGen NT BaseBox
CategoryController
LanguageEnglish

Related product manuals