EasyManuals Logo
Home>ComAp>Controller>InteliGen NT BaseBox

ComAp InteliGen NT BaseBox User Manual

ComAp InteliGen NT BaseBox
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #124 background imageLoading...
Page #124 background image
IGS-NT Communication Guide
124
To configure the converter in the Profibus network, download the description file
www.geindustrial.com/products/software/d485/P48509E5.zip and import it to the Profibus configuration
tool.
Follow instructions in the P485 manual while configuring the converter. The setup wizard incorporated in the
Enervista software will make the setup process much easier, but finally some manual corrections are needed.
Below are some notes specific to the connection with ComAp controllers.
The physical layer for Modbus communication is select table. The selected type (RS232/RS485) and speed
must be same in the P485 and controller, see Controller setup on page 62.
Use RS485 in case more controllers are connected to the P485.
A Device mentioned in the wizard represents a controller type (IG-NT, IM-NT, IS-NT). Once a device is
defined, more nodes of the same type (device) can be created easily.
A modbus network node represents a controller. The slave address must correspond to the Controller
address setpoint of the related controller.
See Modbus Connection (page 129) for details about Modbus, register numbers, sizes etc.
Use triggered update mode for writing objects (registers) to the controller. Never use cyclic update
mode!
8.7.3 Setup example (using wizard)
1. Select wizard
2. Select fieldbus type.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliGen NT BaseBox and is the answer not in the manual?

ComAp InteliGen NT BaseBox Specifications

General IconGeneral
BrandComAp
ModelInteliGen NT BaseBox
CategoryController
LanguageEnglish

Related product manuals