IGS-NT Communication Guide
84
Modem to RS232 on controller/I-LB
Comms settings: MODEM (HW) or I-LB jumper HW control
DB9 Male to DB9 Female
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
9 9
Comms settings: MODEM (SW) or I-LB jumper SW control
DB9 Male to DB9 Female
2 2
3 3
5 5
7.1.5 USB cable
Use standard USB A-B cable (distance up to 5 meters).
IMPORTANT: Use shielded USB cable only! (ComAp order code: USB-LINK CABLE 1.8m).
Note: To use USB connection it is necessary to install drivers on your PC.
The drivers can be downloaded from the website www.ftdichip.com/Drivers/VCP.htm.
Download the driver for your operating system and follow the enclosed instructions.
After successful installation of the driver and connection of the controller or I-LB+ to the PC the new Virtual
Communications Port appears in ComAp PC tools and it is possible to open connection via USB.