Communication Guide, ©ComAp March 2014 93
IGS-NT Communication Guide 03-2014.pdf
Modbus
Register(s)
Com.Obj.
Name
Dim
Type*
Decimals
40289
8196
Mains V L2-N
V
Unsigned16
0
40290
8197
Mains V L3-N
V
Unsigned16
0
40296
8211
Mains freq
Hz
Unsigned16
1
43589
8207
Num starts
Unsigned16
0
43587
8206
Run hours
h
Integer 32
0
46354
Num items alarmlist
Unsigned16
46669
Item 1 alarmlist
String
46694
Item 2 alarmlist
String
46719
Item 3 alarmlist
String
46744
Item 4 alarmlist
String
46769
Item 5 alarmlist
String
46794
Item 6 alarmlist
String
46819
Item 7 alarmlist
String
46844
Item 8 alarmlist
String
46869
Item 9 alarmlist
String
46894
Item 10 alarmlist
String
46919
Item 11 alarmlist
String
46944
Item 12 alarmlist
String
46969
Item 13 alarmlist
String
46994
Item 14 alarmlist
String
47019
Item 15 alarmlist
String
47044
Item 16 alarmlist
String
Read / Write
43027
8315
ControllerMode
Unsigned16
46359
Action argument
Integer32
Write only
24470
24470
User identification number
Unsigned16
24524
24524
Password
Unsigned16
46361
Action command
Unsigned16
* SNMI data types are INTEGER32 for all numerical values except “Run hours”, which is GAUGE32. The column “Type
means how the data shall be interpreted.
Converter settings
Setup of the converter is done via TELNET at port 9999 instead of standard port 21. The default IP
address is 192.168.1.254.
To enter setup mode:
1. Connect the converter to LAN
2. Put command “telnet 192.168.1.254 9999” to the windows command line on any computer
connected to the same LAN
Setup procedure:
1. Press “0” key to change server configuration (converter IP address, netmask, gateway
address etc..)
2. Press “1” key to change device configuration (read/write community, SNMP manager
address*..)
3. Press “9” key to save parameters to the memory and exit setup mode

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliGen NTC and is the answer not in the manual?

ComAp InteliGen NTC Specifications

General IconGeneral
BrandComAp
ModelInteliGen NTC
CategoryController
LanguageEnglish

Related product manuals