CALIBRATING TEMPERATURE SENSORS
The following infield calibration is required for the Temperature Sensor(s):
1. Use a thermometer to verify pool temperature.
2. Use a thermometer to verify solar temperature if applicable.
3. At the Cp3000 Controller, turn on the Pool and let it run for a few minutes.
4. Press the Program Key.
5. Press the Pool Heat Source Key. ADJ 1 will appear on the Display.
6. Use the Pool Temperature Keys to enter the temperature verified in Step 1.
7. Press the Pool Heat Source Key again. If the system incorporates a Solar Temperature Sensor, ADJ 2 will now
appear on the Display. Use the Pool Temperature Keys to enter the temperature verified in step 2.
8. Press the Pool Heat Source Key once more to return the Display to the normal operating mode.