- 30 -
OSV value is set to 42°C and the DIF value to 2°C, the outputs
of the thermostat will be disabled when the temperature mea-
sured by the oor temperature sensor reaches 44°C, and the
outputs will resume normal operation only after the temperature
measured by the oor temperature sensor goes below 40°C.
8.3Calibrationofthetemperaturesensor
The measuring accuracy of the thermometer of the thermostat
is +/- 1°C. The temperature displayed by the thermostat can
be modied in steps of 0.5°C in comparison to the temperature
measured by the temperature sensor, but the modication must
not exceed +/- 5°C.
8.4.Antifreezing
When the antifreezing function of the thermostat is activated, the
thermostat will switch on its output, regardless of any other set-
ting, when the temperature measured by the thermostat goes
below 5°C. When the temperature reaches 7°C, normal opera-
tion of the output is restored (according to the set temperature).
8.5.Memorizingsettingsintheeventofapowerfailure
By means of the Memorizing Settings function of the thermostat
you can select the mode in which the thermostat continues to
operate: