9 Counter Inputs 
The SCADAPack LP has three counter inputs, identified as Counter 0, 1 and 2. Two of the counter 
inputs, Counter 1 and 2, are designed for millivolt level turbine meters. The third, Counter 0, is a 
high level digital input for use with open collector/drain output amplifiers. 
Refer to the appropriate software manual for information on using the SCADAPack LP Counter 
Inputs in application programs.  
•  For TelePACE applications refer to the Register Assignment for SCADAPack LP I/O module 
and  
•  For ISaGRAF applications refer to the I/O Complex Equipment for SCADAPack LP I/O.  
•  For C applications use the readCounter function. 
9.1  Counter Input 0 
Counter Input 0 is used to count contact closures. The input circuitry includes a 1000-ohm resistor 
from the counter input to the 5V power supply. Refer to Figure 7: Counter Input Wiring for an 
example of wiring to an open collector output. 
 
 
5 4 3 2 1 
0 1 2 
P5 – Counters 
GND 
 
Turbine 
Meter 
Sensor 
 
GND 
Turbine 
Meter 
Amplifier 
 
Consult manufacturer of 
amplifier for wiring details. 
 J9   J10   J11  J12 
1 2  1 2 
       Counter 1 input through 
    internal amplifier  
Counter 2 input  
bypassing internal amplifier. 
 
Figure 7: Counter Input Wiring 
9.2  Turbine Meter Counter Inputs 1 and 2 
The SCADAPack LP allows for the direct connection of two turbine meter sensors. These sensors 
produce millivolt outputs and do not require an external pre-amplifier when used with the 
SCADAPack LP. The turbine meter inputs should be used in low noise environments with shielded 
cabling. 
There are four jumper links associated with configuring the inputs for either millivolt signals (direct 
to sensor) or high level signals such as external amplifiers, dry contacts or open collector outputs. 
Refer to Figure 7: Counter Input Wiring for examples of how to configure the jumper links and 
wire the inputs. Counter 1 is shown as a millivolt input with a direct connection to a turbine meter 
SCADAPack LP Hardware Manual 
May 26, 2006   
22