sensor. Note the use of shielded wiring and that the shield is connected at one end only. Counter 2 is 
shown connected to an external turbine meter pre-amplifier. 
When connecting to a turbine meter amplifier the manufacturer may have a specific current 
requirement to power the pre-amplifier. The SCADAPack LP includes a 1000-ohm resistor from the 
counter input to the DC input power source. This is the recommended wiring for a Halliburton Low 
Power Pre-Amp when the SCADAPack LP is powered from 12V. If this resistor is not suitable for 
your external amplifier then do not connect the jumper in either position. On Counter 1, the J11 
jumper would be removed. On Counter 2, the J12 jumper would be removed. Wire the amplifier as 
per the manufacturers recommendations. 
Counter Inputs 1 and 2 can be used with conventional sources such as open collector transistors and 
contacts. The SCADAPack LP includes a 1000-ohm resistor from the counter input to the DC input 
power source. This resistor can be used when the SCADAPack LP is powered from 12V. On 
Counter 1, J11 would be in the External Amplifier or bottom position. On Counter 2, J12 would be 
in the External Amplifier or bottom position. If a higher voltage is used or a pullup current other than 
12V at 1000-ohms is required then the user must wire an external resistor to an appropriate power 
source. On Counter 1, the J11 jumper would be removed. On Counter 2, the J12 jumper would be 
removed. 
 J9  J11 
Internal 
amplifier 
To counter 1 
Counter 1 input 
Internal 1000 
ohms connected 
to Input Voltage 
 J10  J12 
Internal 
amplifier 
To counter 2 Counter 2 input 
Internal 1000 
ohms connected 
to Input Voltage 
12VDC PWR IN 
12VDC PWR 
 
Figure 8: Counter Jumpers 
SCADAPack LP Hardware Manual 
May 26, 2006   
23