MiniWarden/PoolWarden + (PLUS) Operation Manual • www.poolwardentraining.com • 19
t PPM-: Setpoint - 1.0: The alarm will turn on if the sensor is less than the PPM setpoint - the value.
Press Enter to cycle between 0.0, 0.5, 1.0, 1.5, 2.0, 2.5 and 3.0.
t pH+: Setpoint + 0.4: The alarm will turn on if the sensor is greater than the pH setpoint + the value.
Press Enter to cycle between 0.0, 0.1, 0.2, 0.3, 0.4 and 0.5.
t pH-: Setpoint - 0.4: The alarm will turn on if the sensor is less than the pH setpoint - the value. Press
Enter to cycle between 0.0, 0.1, 0.2, 0.3, 0.4 and 0.5.
Remaining alarm conditions
t On If Flow Off FS 1: The alarm will turn on if no flow is detected. Pool1 uses Flow Switch Input 1 and
Pool2 uses Flow Switch Input 3. To turn the alarm status on if no flow is detected for Pool1 simply hit
the Enter Key to change the value from “none” to FS 1 (Flow Switch Input 1). To turn the alarm status
on if no flow is detected for Pool2 simply hit the Enter Key 3 times to change the value from “none” to FS
3.
t On If Overfeed - YES: The alarm will turn on if the daily overfeed or setpoint overfeed has been
reached for the indicated pool including the pH, ORP and Aux relays.
t If DPD Below 10%: With the TrueDPD enabled, this will turn the alarm on if the DPD reagent bottle
drops below 10%. Make sure to set the value in the TrueDPD information screen.
t If DPD Error: If there is an error detected by the TrueDPD sensor such as the clear voltage below 3.50
turn the alarm on.
t Off If Flow Off - none: The PoolWarden will not send alarm notification if no flow is detected. If the
main pump is off then you may not want to get alarm notifications.
t On Delay 00:10:00: The alarm will only turn on if this condition is satisfied for at least 10 Minutes. This
command prevents multiple alarms if the sensor readings are fluctuating back and forth.
t Min Time On 00:00:10: The alarm will be on at least this long giving time for notifications to be sent out.
t Min Time Off 00:00:10: When the alarm turns off, it will be off at least this long.
t Off If Time < 00:00:00: This is a time of day command. Used to disable the alarm in the morning. If not
00:00:00, the alarm will be off from midnight until the time in this command. Use this command if you
don’t want notifications at night.
ORP High Alarm 800
ORP Low Alarm 600
PPM High Alarm 7.0
PPM Low Alarm 1.0
pH High Alarm 8.0
PH Low Alarm 6.0
Temp High Alarm 0
Temp Low Alarm 0
On if Flow Off FS 1
On if Overfeed Yes
Off if Flow off none
If DPD Below 10% Yes
If DPD Error No
On DELAY 00:10:00
MinTime On 00:00:10
MinTimeOff 00:00:10
OffIfTime< 00:00:00
OffIfTime> 00:00:00
with TrueDPD PPM
ORP High Alarm 800
ORP Low Alarm 600
pH High Alarm 8.0
pH Low Alarm 7.0
Temp High Alarm 0
Temp Low Alarm 0
On if Flow Off FS 1
On if Overfeed Yes
Off if Flow off none
On DELAY 00:10:00
MinTime On 00:00:10
MinTimeOff 00:00:10
OffIfTime< 00:00:00
OffIfTime> 00:00:00
Alarm Settings
ORP+: Setpoint + 100
ORP-: Setpoint - 100
PPM+: Setpoint + 3.0
PPM-: Setpoint - 1.0
pH+: Setpoint + 0.4
PH-: Setpoint - 0.4
Temp High Alarm 0
Temp Low Alarm 0
On if Flow Off FS 1
On if Overfeed Yes
Off if Flow off none
If DPD Below 10% Yes
If DPD Error No
On DELAY 00:10:00
MinTime On 00:00:10
MinTimeOff 00:00:10
OffIfTime< 00:00:00
OffIfTime> 00:00:00
with TrueDPD PPM
Absolute Alarms Delta Alarms