CF3000 - USER MANUAL
26
Output 4: Disablement of the Fire Routing Equipment
This output is ON to indicator that the fire r
outing equipment has been disabled either by the
CF3000 Control and indicating equipment or the fire brigade panel.
Output 5: Reset from Fire Alarm Condition
This output is ON to indicate that the CF3000 control and indicating equipment is in alarm
condition. This output will remain on for at least 15mins after reset or when the reset has
been activated from the fire alarm brigade panel
Output 6: Disablement of Sounders
This output is ON to indicate that the sounders have been disabled either by the CF3000
control and indicating equipment or the fire brigade panel
Inputs
Input 1: Reset
This input is used to reset the control and indicating equipment
Input 2: Testing of Fire Routing Equipment
This input is used to test the output to the fire routing equipment
Input 3: Disablement of the Fire Routing Equipment
This input is used to disable the fire routing equipment if the CF3000. Once the FRE is
disabled from this interface, it can never be enabled from the CF3000 control panel
Input 4: Disablement of the Fire Protecting Equipment
This input is used to disable the fire protecting equipment of the CF3000. Once the FRE is
disabled from this interface, it can never be enabled from the CF3000 control panel
Input 5: Disablement of Sounders
This input is used to disable the sounders of the CF3000. The disablement of sounders from
the fire brigade panel can be re-abled from the CF3000 control panel only when the system
is not alarm state.
Section 1 - System Installation and Design