E.2: XSL-FA-01 Edge Filter Specifications
Voltage, maximum 373 Vdc
Input
Current, maximum 20 Adc
Voltage, maximum 373 Vdc
Output
Current, maximum 20 Adc
Peak Current/Peak Current Time 40 Adc for 1 second
Rise/Fall Time 500 nS (typical)
Differential Mode Inductance 82 RH per phase, 162 uH phase-phase (nominal)
Common Mode Inductance 220 RH (nominal)
Nominal Resistance 27 milliohms per leg, 54 milliohms phase-phase (nominal)
Agency Approvals UL508C, EN60204
E.3: Thermal Considerations
Cooling Requirements
When used with XSL-230-18 or XSL 230-36 amplifiers, the XSL-FA-01 operates below maximum
temperature values, and thus requires no cooling fan.
When used with XSL-40 amplifiers running continuous currents greater than 12 Adc,
the XSL-FA-01 should be cooled with an external fan. The fan should have a flow rate of at least
110 CFM. The filter has been tested using the Comair Rotron MD24B2 24 Vdc powered fan.
Fan Mounting Guidelines
Most of the filter’s heat is transferred to ambient air, rather than through the heat plate. Thus, it is
very important to mount the filter and fan in such a way that the fan can blow up through the filter’s
cover slots. Mount the filter on edge and mount the fan below it so that it blows up through the
cover slots.
There is no heatsink option for the XSL-FA-01 edge filter.