Xenus XSL User Guide Quick Setup with CME 2
Copley Controls Corp. 93
5.8: Amplifier Configuration
5.8.1: Digital Inputs
5.8.1.1 Click Input/Output ( ) on the Main screen to open the Input/Output screen.
Lo/Hi: Indicates state of output.
Red light: inhibited motion or active input, depending on input function.
Grey light: motion not inhibited.
No light: not configured.
Indicates input is used as a CAN address bit.
5.8.1.2 Enter the following options:
Option Description
Pull up +5 V Internally pulls the group of inputs up to internal +5 V.
Pull down Internally pulls the group of inputs down to signal ground.
Debounce
Time
Sets the input debounce time.
Range of accepted values: 0 to 10,000 mSec.
For more information, see Debounce Time (p. 42).
IN1-IN12 Select the function for the input. See Digital Input Functions (p. 94) for input function
descriptions.