26
Littelfuse KLKD fuse series are recommended. The detailed information is
available for customers to find and download from
http://www.littelfuse.com/.
(b) Insert the cables through steel conduits and strip the skin 0.4 inch off
the cables as shown in Figure 3-10:
Figure 3-10 Wire stripping of DC input
(c) Crimp the terminal as shown in Figure 3-11:
Figure 3-11 Terminal crimping of DC input
(d) The order of wire connection from left to right is PV1+, PV1-, PV2+,
PV2-. Connect the PV1- and PV2- to the corresponding fuse socket of the
negative pole and connect the PV1+ and PV2+ to the corresponding fuse
socket of the positive pole with the torque value of 1.2N-M (10.6Lb-In.).