10 | Configuration
Installer reference guide
144
EPGA11~16DAV3(7) + EAVZ16S18+23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
# Code Description
[9.8.3] [D-05] Allow pump:
0 No: Pump is forced off
1 Yes: No limitation
Allowed heaters during preferential kWh rate power supply
Do NOT use 1 or 3.
[D‑00] Backup heater Compressor
0 Forced OFF Forced OFF
2 Allowed
Power consumption control
Power consumption control
See "6 Application guidelines" [4 30] for detailed information about this
functionality.
# Code Description
[9.9.1] [4-08] Power consumption control:
0 No: Disabled.
1 Continuous: Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
2 Inputs: Enabled: You can set up to four
different power limitation values (in A or kW)
to which the system power consumption will
be limited when the corresponding digital
input asks.
[9.9.2] [4-09] Type:
0 Amp: The limitation values are set in A.
1 kW: The limitation values are set in kW.
Limit when [9.9.1]=Continuous and [9.9.2]=Amp:
# Code Description
[9.9.3] [5-05] Limit: Only applicable in case of full time
current limitation mode.
0A~50A
Limits when [9.9.1]=Inputs and [9.9.2]=Amp:
# Code Description
[9.9.4] [5-05] Limit 1: 0A~50A
[9.9.5] [5-06] Limit 2: 0A~50A
[9.9.6] [5-07] Limit 3: 0A~50A
[9.9.7] [5-08] Limit 4: 0A~50A
Limit when [9.9.1]=Continuous and [9.9.2]=kW: