10 | Configuration
Installer reference guide
145
EPGA11~16DAV3(7) + EAVZ16S18+23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
# Code Description
[9.9.8] [5-09] Limit: Only applicable in case of full time
power limitation mode.
0kW~20kW
Limits when [9.9.1]=Inputs and [9.9.2]=kW:
# Code Description
[9.9.9] [5-09] Limit 1: 0kW~20kW
[9.9.A] [5-0A] Limit 2: 0kW~20kW
[9.9.B] [5-0B] Limit 3: 0kW~20kW
[9.9.C] [5-0C] Limit 4: 0kW~20kW
Priority heater
# Code Description
[9.9.D] [4-01] Power consumption control DISABLED
[4‑08]=0
▪ 0 None : Backup heater and booster heater
can operate simultaneously.
▪ 1 Booster heater: The booster heater is
prioritised.
▪ 2 Backup heater: The backup heater is
prioritised.
Power consumption control ENABLED
[4‑08]=1/2
▪ 0 None : Depending on the power limitation
level, the booster heater will be limited first,
before the backup heater is limited.
▪ 1 Booster heater: Depending on the
power limitation level, the backup heater will
be limited first, before the booster heater is
limited.
▪ 2 Backup heater: Depending on the power
limitation level, the booster heater will be
limited first, before the backup heater is
limited.
Note: In case power consumption control is DISABLED (for all models) the setting
[4‑01] defines whether backup heater and booster heater can operate
simultaneously, or if the booster heater/backup heater has priority over the
backup heater/booster heater.
In case power consumption control is ENABLED, the setting [4‑01] defines the
priority of the electrical heaters depending on applicable limitation.
Energy metering
Energy metering
If energy metering is performed by the use of external power meters, configure the
settings as described below. Select the pulse frequency output of each power
meter in accordance with the power meter specifications. It is possible to connect