5 Application guidelines
Installer reference guide
16
ERGA04~08DAV3(A) + EHVH04+08S23DAV
Daikin Altherma – Low temperature split
4P499573-1 – 2017.12
▪ Connect X1 and X2 (changeover to external heat source) on the
digital I/O PCB to the auxiliary boiler thermostat.
▪ To setup the heat emitters, see "5.2Setting up the space heating
system"on page10.
Configuration
Via the user interface (quick wizard):
▪ Set the use of a bivalent system as external heat source.
▪ Set the bivalent temperature and hysteresis.
NOTICE
▪ Make sure the bivalent hysteresis has enough
differential to prevent frequent changeover between
indoor unit and auxiliary boiler.
▪ Because the outdoor temperature is measured by the
outdoor unit air thermistor, install the outdoor unit in the
shadow so that it is NOT influenced or turned ON/OFF
by direct sunlight.
▪ Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the
auxiliary boiler for more information.
Changeover to external heat source decided by an auxiliary
contact
▪ Only possible in external room thermostat control AND one
leaving water temperature zone (see "5.2 Setting up the space
heating system"on page10).
▪ The auxiliary contact can be:
▪ An outdoor temperature thermostat
▪ An electricity tariff contact
▪ A manually operated contact
▪ …
▪ Setup: Connect the following field wiring:
L
N
H
Com
A
K2AK1A
X2M
B
TI
K2AK1A
Indoor/Auto/Boiler
35 30 X Y
Indoor
B
TI
Boiler thermostat input
A Auxiliary contact (normal closed)
H Heating demand room thermostat (optional)
K1A Auxiliary relay for activation of indoor unit (field supply)
K2A Auxiliary relay for activation of boiler (field supply)
Indoor Indoor unit
Auto Automatic
Boiler Boiler
NOTICE
▪ Make sure the auxiliary contact has enough differential
or time delay to prevent frequent changeover between
indoor unit and auxiliary boiler.
▪ If the auxiliary contact is an outdoor temperature
thermostat, install the thermostat in the shadow so that
it is NOT influenced or turned ON/OFF by direct
sunlight.
▪ Frequent changeover may cause corrosion of the
auxiliary boiler. Contact the manufacturer of the
auxiliary boiler for more information.
5.4 Setting up the domestic hot water
tank
The DHW tank is integrated in the indoor unit, and contains a 2.4kW
anti-legionella heater. The anti-legionella heater contains 2 safeties:
a thermal cut-out and a thermal fuse. If a certain temperature is
exceeded, the safeties deactivate the anti-legionella heater.
5.4.1 System layout – Integrated DHW tank
FHL1
FHL2
FHL3
M
UI
a b c hh if
e
g
d
a Outdoor unit
b Indoor unit
c Heat exchanger
d Anti-legionella heater
e Pump
f Motorised 3‑way valve
g DHW tank
h Shut-off valve
i Collector (field supply)
FHL1...3 Underfloor heating
UI User interface
5.4.2 Selecting the volume and desired
temperature for the DHW tank
People experience water as hot when its temperature is 40°C.
Therefore, the DHW consumption is always expressed as equivalent
hot water volume at 40°C. However, you can set the DHW tank
temperature at a higher temperature (example: 53°C), which is then
mixed with cold water (example: 15°C).
Selecting the desired temperature for the DHW tank consists of:
1 Determining the DHW consumption (equivalent hot water
volume at 40°C).
2 Determining the desired temperature for the DHW tank.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption
(equivalent hot water volume at 40°C) using typical water volumes:
Question Typical water volume
How many showers are needed
per day?
1shower = 10min×10l/min =
100l
How many baths are needed per
day?
1bath = 150l
How much water is needed at the
kitchen sink per day?
1sink = 2min×5l/min = 10l
Are there any other domestic hot
water needs?
—
Example: If the DHW consumption of a family (4 persons) per day
is as follows:
▪ 3 showers
▪ 1 bath
▪ 3 sink volumes