8 Configuration
Installer reference guide
53
ERGA04~08DAV3(A) + EHVH04+08S23DAV
Daikin Altherma – Low temperature split
4P499573-1 – 2017.12
7 Select Sunday.
8 Select Paste.
Result:
Mon
Sat
Wed
Fri
Thu
Tue
Sun
User defined 1
C
To rename the schedule:
INFORMATION
Not all schedules can be renamed.
1 Select the name of the current schedule.
Mon
Sat
Wed
Fri
Thu
Tue
Sun
User defined 1
2 Select the Rename option.
3 Browse through the character list and confirm the
selected character.
4 Confirm the new name.
8.4 Settings menu
You can set additional settings using the main menu screen and its
submenus. The most important settings are presented here.
8.4.1 Malfunction
In case of a malfunction,
or will appear on the home screen.
If you open the menu screen, the Malfunctioning menu will now be
visible. Open the menu to see the error code. Press
to get more
information about the error.
8.4.2 Room
Setpoint screen
You can control the room temperature of the main zone with the
setpoint screen, also see "8.3.5Setpoint screen"on page51.
Schedule
In this menu item you can indicate if the room temperature is
controlled with a schedule or not.
# Code Description
[1.1] N/A Schedule
▪ 0 No: Room temperature is controlled
by the user.
▪ 1 Yes: Room temperature is controlled
with a schedule and can be modified
by the user.
Heating schedule
This is available for all models.
You can set the room temperature heating schedule using the
schedule screen. For more information about this screen, see
"8.3.8Schedule screen: Example"on page51.
Antifrost
Room frost protection [1.4] prevents the room from getting too cold.
This setting behaves differently depending on the set unit control
method [2.9]. Perform actions according to the table below.
Main zone unit control
method [2.9]
Description
Leaving water temperature
control ([C 07]=0)
Room frost protection is NOT
guaranteed.
External room thermostat
control ([C 07]=1)
Allow for the external room
thermostat to take care of room
frost protection:
▪ Turn ON [C.2]: Space heating/
cooling
Room thermostat control ([C
07]=2)
Allow for the user interface used as
room thermostat to take care of
room frost protection:
▪ Choose [1.4.1]=1: Room >
Antifrost > Activation > Yes
▪ Set the room antifrost setpoint
([1.4.2]): Room > Antifrost >
Room setpoint
NOTICE
If the system does NOT contain a backup heater, then:
▪ Make sure that the room antifrost control is activated
([2-06]=1).
▪ Do NOT change the default room antifrost temperature
[2-05].
▪ Make sure that the water pipe freeze prevention is
activated ([4-04]≠2).
INFORMATION
If a U4 error occurs, room frost protection is NOT
guaranteed.
For more detailed information about room frost protection in relation
to the applicable unit control method, see the sections below:
Leaving water temperature control ([C‑07]=0)
Under leaving water temperature control, room frost protection is
NOT guaranteed. However, if room antifrost [1.4] is activated, limited
frost protection by the unit is possible:
If... Then...
Space heating/cooling is OFF
and the outdoor ambient
temperature drops below 4°C
The unit will supply leaving water
to the heat emitters to heat up
the room again, and the leaving
water temperature setpoint will
be lowered.
Space heating/cooling is ON and
the operation mode is "heating"
The unit will supply leaving water
to the heat emitters to heat up
the room according to normal
logic.
External room thermostat control ([C‑07]=1)
Under external room thermostat control, room frost protection is
guaranteed by the external room thermostat, provided that Space
heating/cooling [C.2] is turned ON and the emergency setting [9.5] is
set to automatic.
In case of one leaving water temperature zone:
Final English - Tanslations in progress