EasyManua.ls Logo

Daikin Altherma EHVH04S23DAV - To Provide Drainage

Daikin Altherma EHVH04S23DAV
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Installation
Installer reference guide
33
ERGA04~08DAV3(A) + EHVH04+08S23DAV
Daikin Altherma – Low temperature split
4P499573-1 – 2017.12
3
2
1
a a
a Air outlet
NOTICE
Properly align the unit. Make sure the backside of the unit
does NOT protrude.
3 Remove the protective cardboard and instruction sheet.
a
b
a Protective cardboard
b Instruction sheet
7.3.5 To provide drainage
Make sure that condensation water can be evacuated properly.
Install the unit on a base to make sure that there is proper
drainage in order to avoid ice accumulation.
Prepare a water drainage channel around the foundation to drain
waste water away from the unit.
Avoid drain water flowing over the footpath, so that it does NOT
become slippery in case of ambient freezing temperatures.
If you install the unit on a frame, install a waterproof plate within
150 mm of the bottom side of the unit in order to prevent water
from getting into the unit and to avoid drain water dripping (see the
following figure).
NOTICE
If the drain holes of the outdoor unit are blocked up,
provide space of at least 300mm below the outdoor unit.
Drain pan. You can use the drain pan option (EKDP008D) to
gather the drain water. For the complete installation instructions,
see the installation manual of the drain pan. In short, the drain pan
must be installed level (with a tolerance of at all sides) and as
follows:
b
a
c
a Drain pan
b U-beams
c Drain hole insulation
355 mm
600 mm
Drain pan heater. You can use the drain pan heater option
(EKDPH008CA) to prevent freezing-up of the drain pan. For the
installation instructions, see the installation manual of the drain
pan heater.
Non-heated drain tube. When using the drain pan heater without
drain tube or with a non-heated drain tube, remove the drain hole
insulation (Item c on the illustration).
7.3.6 To prevent the outdoor unit from falling
over
In case the unit is installed in places where strong wind can tilt the
unit, take following measure:
1 Prepare 2 cables as indicated in the following illustration (field
supply).
2 Place the 2 cables over the outdoor unit.
3 Insert a rubber sheet between the cables and the outdoor unit
to prevent the cable from scratching the paint (field supply).
4 Attach the cable’s ends. Tighten those ends.
Final English - Tanslations in progress