5 Application guidelines
Installer reference guide
12
ERGA04~08DAV3(A) + EHVH04+08S23DAV
Daikin Altherma – Low temperature split
4P499573-1 – 2017.12
The space operation mode is sent to the heatpump convectors by
one digital output on the indoor unit (X2M/4 and X2M/3).
INFORMATION
When using multiple heat pump convectors, make sure
each one receives the infrared signal from the remote
controller of the heatpump convectors.
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
Number of water temperature
zones:
#: [4.4]
Code: [7-02]
0 (Single zone): Main
External room thermostat for the
main zone:
#: [2.A]
Code: [C-05]
1 (1 contact): When the used
external room thermostat or
heatpump convector can only
send a thermo ON/OFF
condition.
Benefits
Efficiency. Optimal energy efficiency because of the interlink
function.
Stylish.
Combination: Underfloor heating + Heatpump
convectors
Space heating is provided by:
The underfloor heating
The heatpump convectors
Setup
B
A
a
A Main leaving water temperature zone
B One single room
a Remote controller of the heatpump convectors
The heat pump convectors are directly connected to the indoor
unit.
The desired room temperature is set via the remote controller of
the heatpump convectors.
The space heating demand signal is sent to one digital input on
the indoor unit (X2M/35 and X2M/30).
The space operation mode is sent to the heatpump convectors by
one digital output on the indoor unit (X2M/4 and X2M/3).
Configuration
Setting Value
Unit temperature control:
#: [2.9]
Code: [C-07]
1 (External room thermostat):
Unit operation is decided by the
external thermostat.
Number of water temperature
zones:
#: [4.4]
Code: [7-02]
0 (Single zone): Main
External room thermostat for the
main zone:
#: [2.A]
Code: [C-05]
1 (1 contact): When the used
external room thermostat or
heatpump convector can only
send a thermo ON/OFF
condition.
Benefits
Efficiency. Under floor heating has the best performance with
Altherma LT.
Comfort. The combination of the two heat emitter types provides
excellent heating comfort of the underfloor heating.
5.2.2 Multiple rooms – OneLWT zone
If only one leaving water temperature zone is needed because the
design leaving water temperature of all heat emitters is the same,
you do NOT need a mixing valve station (cost effective).
Example: If the heat pump system is used to heat up one floor
where all the rooms have the same heat emitters.
Underfloor heating or radiators – Thermostatic
valves
If you are heating up rooms with under floor heating or radiators, a
very common way is to control the temperature of the main room by
using a thermostat (this can either be the user interface or an
external room thermostat), while the other rooms are controlled by
so-called thermostatic valves, which open or close depending on the
room temperature.
Setup
The underfloor heating of the main room is directly connected to
the indoor unit.
The room temperature of the main room is controlled by the user
interface used as a room thermostat (optional equipment
EKRUDAS).
A thermostatic valve is installed before the underfloor heating in
each of the other rooms.
INFORMATION
Mind situations where the main room can be heated by
another heating source. Example: Fireplaces.
Final English - Tanslations in progress