7 Installation
Installer reference guide
34
ERGA04~08DAV3(A) + EHVH04+08S23DAV
Daikin Altherma – Low temperature split
4P499573-1 – 2017.12
7.4 Mounting the indoor unit
7.4.1 About mounting the indoor unit
When
You have to mount the outdoor and indoor unit before you can
connect the refrigerant and water piping.
Typical workflow
Mounting the indoor unit typically consists of the following stages:
1 Installing the indoor unit.
7.4.2 Precautions when mounting the indoor
unit
INFORMATION
Also read the precautions and requirements in the
following chapters:
General safety precautions
Preparation
7.4.3 To install the indoor unit
1 Lift the indoor unit from the pallet and place it on the floor. Also
see "3.3.3To handle the indoor unit"on page8.
2 Connect the drain hose to the drain. See "7.8.5To connect the
drain hose to the drain"on page40.
3 Slide the indoor unit into position.
4 Adjust the height of the leveling feet to compensate for floor
irregularities. The maximum allowed deviation is 1°.
≤1°
NOTICE
Do NOT tilt the unit forwards:
7.5 Connecting the refrigerant piping
7.5.1 About connecting the refrigerant piping
Before connecting the refrigerant piping
Make sure the outdoor and indoor unit are mounted.
Typical workflow
Connecting the refrigerant piping involves:
Connecting the refrigerant piping to the outdoor unit
Connecting the refrigerant piping to the indoor unit
Insulating the refrigerant piping
Keeping in mind the guidelines for:
Pipe bending
Flaring pipe ends
Brazing
Using the stop valves
7.5.2 Precautions when connecting the
refrigerant piping
INFORMATION
Also read the precautions and requirements in the
following chapters:
General safety precautions
Preparation
DANGER: RISK OF BURNING
CAUTION
Do NOT use mineral oil on flared part.
Do NOT reuse piping from previous installations.
NEVER install a drier to this R32 unit to guarantee its
lifetime. The drying material may dissolve and damage
the system.
Final English - Tanslations in progress