7 Installation
Installer reference guide
43
ERGA04~08DAV3(A) + EHVH04+08S23DAV
Daikin Altherma – Low temperature split
4P499573-1 – 2017.12
6 Connect an earth leakage circuit breaker and fuse to the power
supply line.
7.9.7 To connect the electrical wiring on the
indoor unit
1 To open the indoor unit, see "7.2.3To open the indoor unit"on
page30 and "7.2.4To open the switch box cover of the indoor
unit"on page30.
2 The wiring enters the unit from the top:
b+c ad
a, b, c Field wiring (see table below)
d Factory-mounted cable for power supply of anti-legionella
heater
3 Routing of the wiring inside the unit should be as follows. Fix
the cable to the cable rail using cable ties:
a
b+c
WARNING
Make sure that the electrical wiring does NOT touch the
refrigerant gas pipe, which can be very hot.
a
a Refrigerant gas pipe
Routing Possible cables (depending on unit type
and installed options)
a
Low voltage
Preferential power supply contact
User interface used as room thermostat
(option)
Power consumption digital inputs (field
supply)
Outdoor ambient temperature sensor
(option)
Indoor ambient temperature sensor
(option)
Electrical meters (field supply)
Safety thermostat (field supply)
Backup heater thermistor (backup heater
option)
b
High voltage power
supply
Interconnection cable
Normal kWh rate power supply
Preferential kWh rate power supply
c
High voltage control
signal
Heat pump convector (option)
Room thermostat (option)
Shut-off valve (field supply)
Domestic hot water pump (field supply)
Alarm output
Changeover to external heat source
control
Space heating operation control
Backup heater thermal protector + backup
heater connection (backup heater option)
d
High voltage power
supply (factory-
mounted cable)
Power supply for anti-legionella heater
CAUTION
Do NOT push or place redundant cable length in the unit.
4 Seal the low voltage wiring intake using the sealing tape
(delivered as accessory).
Without low voltage cables With low voltage cables
7.9.8 To connect the main power supply
1 Connect the main power supply.
In case of normal kWh rate power supply