EasyManua.ls Logo

Daikin Altherma EHVH04S23DAV - To Connect the Recirculation Piping; To Fill the Water Circuit; To Fill the Domestic Hot Water Tank; To Insulate the Water Piping

Daikin Altherma EHVH04S23DAV
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Installation
Installer reference guide
41
ERGA04~08DAV3(A) + EHVH04+08S23DAV
Daikin Altherma – Low temperature split
4P499573-1 – 2017.12
Option 2: Through the right side panel
1
T25
3
2
7.8.6 To fill the water circuit
To fill the water circuit, use a field supply filling kit. Make sure you
comply with the applicable legislation.
INFORMATION
Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.
7.8.7 To fill the domestic hot water tank
1 Open every hot water tap in turn to purge air from the system
pipe work.
2 Open the cold water supply valve.
3 Close all water taps after all air is purged.
4 Check for water leaks.
5 Manually operate the field-installed pressure relief valve to
ensure a free water flow through the discharge pipe.
NOTICE
To operate the system, the domestic hot water tank needs
to be filled completely. Turning on the system when the
tank is not full can damage the integrated anti-legionella
heater and cause electrical errors.
7.8.8 To insulate the water piping
The piping in the complete water circuit MUST be insulated to
prevent condensation during defrost operation and reduction of the
heating capacity.
If the temperature is higher than 30°C and the humidity is higher
than RH80%, the thickness of the insulation materials should be at
least 20 mm to prevent condensation on the surface of the
insulation.
7.9 Connecting the electrical wiring
7.9.1 About connecting the electrical wiring
Before connecting the electrical wiring
Make sure:
The refrigerant piping is connected and checked
The water piping is connected
Typical workflow
Connecting the electrical wiring typically consists of the following
stages:
1 Making sure the power supply system complies with the
electrical specifications of the heat pump.
2 Connecting the electrical wiring to the outdoor unit.
3 Connecting the electrical wiring to the indoor unit.
4 Connecting the main power supply.
5 Connecting the backup heater power supply.
6 Connecting the shut–off valves.
7 Connecting the electrical meters.
8 Connecting the domestic hot water pump.
9 Connecting the alarm output.
10 Connecting the space cooling/heating ON/OFF output.
11 Connecting the changeover to an external heat source.
12 Connecting the power consumption digital inputs.
13 Connecting the safety thermostat.
7.9.2 About electrical compliance
Only for ERGA04~08DAV3 (not for ERGA04~08DAV3A)
Equipment complying with EN/IEC 61000‑3‑12 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16A and ≤75A per phase.).
Only for indoor units with backup heater as an option
See "7.9.9 To connect the backup heater power supply" on
page44.
7.9.3 Precautions when connecting the
electrical wiring
INFORMATION
Also read the precautions and requirements in the
following chapters:
General safety precautions
Preparation
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
7.9.4 Guidelines when connecting the electrical
wiring
Keep the following in mind:
If stranded conductor wires are used, install a round crimp-style
terminal on the end of the wire. Place the round crimp-style
terminal on the wire up to the covered part and fasten the terminal
with the appropriate tool.
b a
a Stranded conductor wire
b Round crimp-style terminal
Use the following methods for installing wires:
Final English - Tanslations in progress

Table of Contents

Other manuals for Daikin Altherma EHVH04S23DAV

Related product manuals