8 Configuration
Installer reference guide
69
ERGA04~08DAV3(A) + EHVH04+08S23DAV
Daikin Altherma – Low temperature split
4P499573-1 – 2017.12
Timers for simultaneous space and domestic hot water
operation request
# Code Description
[9.6.4] [8-02] Anti-recycle timer: Minimum time
between two cycles for domestic hot
water. The actual anti-recycling time also
depends on setting [8-04].
Range: 0~10 hours
Remark: The minimum time is 0.5 hours
even when the selected value is 0.
[9.6.5] N/A Minimum running timer:
Do NOT change.
[9.6.6] [8-01] Maximum running timer for domestic hot
water operation. Domestic hot water
heating stops even when the target
domestic hot water temperature is NOT
reached. The actual maximum running
time also depends on setting [8-04].
When Control=Room thermostat: This
preset value is only taken into account
if there is a request for space heating.
If there is NO request for space
heating, the tank is heated until the
setpoint has been reached.
When Control≠Room thermostat: This
preset value is always taken into
account.
Range: 5~95 minutes
[9.6.7] [8-04] Additional timer: Additional running time
for the maximum running time depending
on the outdoor temperature [4-02].
Range: 0~95 minutes
[8-02]: Anti-recycle timer
t
1
0
1
0
[8-01] [8-02]
1 Heat pump domestic water heating mode (1=active, 0=not
active)
2 Hot water request for heat pump (1=request, 0=no request)
t Time
[8-04]: Additional timer at [4-02]
t
T
A
0
[8-01]
[5-03] [4-02]
[8-02]
[8-01]+
[8-04]
T
A
Ambient (outdoor) temperature
t Time
Anti-recycle timer
Maximum running time domestic hot water
Water pipe freeze prevention
Only relevant for installations with water piping outdoors. This
function tries to protect outdoor water piping from freezing.
# Code Description
[9.7] [4-04] Water pipe freeze prevention:
0: Intermittent
1: Continuous
2: Off
NOTICE
If the system does NOT contain a backup heater, then:
Make sure that the room antifrost control is activated
([2-06]=1).
Do NOT change the default room antifrost temperature
[2-05].
Make sure that the water pipe freeze prevention is
activated ([4-04]≠2).
Benefit kWh power supply
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/9+10) as the safety
thermostat. It is only possible for the system to have
EITHER preferential kWh rate power supply OR a safety
thermostat.
# Code Description
[9.8.1] [D-01] Connection to a Benefit kWh power
supply or a Safety thermostat
0 No: The outdoor unit is connected to
a normal power supply.
1 Open: The outdoor unit is connected
to a preferential kWh rate power
supply. When the preferential kWh
rate signal is sent by the electricity
company, the contact will open and
the unit will go in forced off mode.
When the signal is released again, the
voltage-free contact will close and the
unit will restart operation. Therefore,
always enable the auto restart
function.
2 Closed: The outdoor unit is
connected to a preferential kWh rate
power supply. When the preferential
kWh rate signal is sent by the
electricity company, the contact will
close and the unit will go in forced off
mode. When the signal is released
again, the voltage-free contact will
open and the unit will restart
operation. Therefore, always enable
the auto restart function.
3 Safety thermostat: A safety
thermostat is connected to the system
(normal closed contact)
Final English - Tanslations in progress