Breadcrumb Field code Setting name Range, step
Default valu
e
Date Value
Installer setting at variance with
default value
Field settings table
4.7 [9-0D] R/W 0~8, step:1
0 : No limitation
1~4 : 50~80%
5~8 : 50~80% during sampling
6
Space heating / cooling
4.9 [F-00] R/W
0: Restricted
1: Allowed
4.A [D-03] R/W 0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
4.B [9-04] R/W 1~4°C, step: 1°C
1°C
4.C [2-06] R/W 0: Disabled
1: Enabled
Tank
5.2 [6-0A] R/W 30~[6-0E]°C, step: 1°C
60°C
5.3 [6-0B] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
5.4 [6-0C] R/W 30~min(50, [6-0E])°C, step: 1°C
45°C
5.6 [6-0D] R/W 0: Reheat only
1: Reheat + sched.
2: Scheduled onl
y
└─ Disinfection
5.7.1 [2-01] R/W 0: No
1: Yes
5.7.2 [2-00] R/W 0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunda
y
5.7.3 [2-02] R/W 0~23 hour, step: 1 hour
1
5.7.4 [2-03] R/O 55~75°C, step: 5°C
70°C
5.7.5 [2-04] R/W 5~60 min, step: 5 min
10 min
Tank
5.8 [6-0E] R/W 40~65°C, step: 1°C
65°C
5.9 [6-00] R/W 2~40°C, step: 1°C
25°C
5.A [6-08] R/W
2~20°C, step: 1°C
10°C
5.B R/W
0: Fixed
1: Weather de
p
endent
└─ WD curve
5.C [0-0B] R/W 35~[6-0E]°C, step: 1°C
55°C
5.C [0-0C] R/W 45~[6-0E]°C, step: 1°C
65°C
5.C [0-0D] R/W 10~25°C, step: 1°C
15°C
5.C [0-0E] R/W -40~5°C, step: 1°C
-10°C
Tank
5.D [6-01] R/W 0~10°C, step: 1°C
2°C
User settings
└─ Quiet
7.4.1 R/W
0: OFF
1: Quiet
2: More quiet
3: Most quiet
4: Automatic
└─ Electricity price
7.5.1 R/W 0,00~990/kWh
1/kWh
7.5.2 R/W 0,00~990/kWh
1/kWh
7.5.3 R/W 0,00~990/kWh
1/kWh
User settings
7.6 R/W 0,00~990/kWh
0,00~290/MBtu
1,0/kWh
Installer settings
└─ Configuration wizard
└─ System
9.1 [E-03] R/W
0: No heater
1: External heater
2: 3V
3: 6V
4: 9W
9.1 [E-05]
[E-06]
[E-07]
R/O
3: Integrated
9.1 [4-06] R/W
0: Manual
1: Automatic
9.1 [7-02] R/W
0: Single zone
1: Dual zone
└─ Backup heater
9.1 [5-0D] R/O 0~2
0: 230V, 1~
Duration
Tank setpoint
Hysteresis
Hysteresis
Setpoint mode
Leaving water value for high ambient temp. for DHW WD curve.
Leaving water value for low ambient temp. for DHW WD curve.
BUH type
Low ambient temp. for DHW WD curve.
Gas price
Pump limitation
Overshoot
Maximum
Heat up mode
Reheat setpoint
Eco setpoint
Comfort setpoint
Start time
Pump outside range
Antifrost
Increase around 0°C
Operation day
High ambient temp. for DHW WD curve.
Emergency
Margin
Activation
High
Medium
Low
Domestic hot water
Number of zones
Voltage
Activation
(#) Setting is not applicable for this unit. 4P499575-1A - 2017.11
Final English - Tanslations in progress